R-12 on the EPA 608 Exam
R-12 is a CFC with ASHRAE safety class A1 (lower toxicity, no flame propagation), an ozone depletion potential of 1.0 and a global warming potential of 10,900. EPA Section 608 treats it as a medium-pressure refrigerant.
| Type | CFC |
| ASHRAE safety class | A1 (lower toxicity, no flame propagation) |
| Ozone depletion potential (ODP) | 1.0 |
| Global warming potential (GWP, 100-year) | 10,900 |
| EPA 608 pressure class | Medium pressure |
| Where you meet it | Old household refrigerators and old vehicle air conditioning. |
Recovery and evacuation level for R-12
EPA names R-12 as a medium-pressure refrigerant. With recovery equipment made on or after November 15, 1993, recover to 10 inches of mercury under 200 lb of refrigerant, 15 inches at 200 lb or more before opening or disposing of the appliance.
Leak repair rules
This is an ozone-depleting refrigerant. Appliances with 50 lb or more fall under the leak repair rule in 40 CFR 82.157 (10% comfort cooling, 20% commercial refrigeration, 30% industrial process). These rates are tested on the exam.
Where R-12 shows up on the exam
Most often in Core and Type I. Practice those sections, then come back to the numbers above.
R-12 compared
- R-12 vs R-134a: safety class A1 vs A1, GWP 10,900 vs 1,430, ODP 1.0 vs 0.
- R-12 vs R-11: safety class A1 vs A1, GWP 10,900 vs 4,750, ODP 1.0 vs 1.0.
Lessons that cover R-12
- Ozone depletion, global warming and refrigerant families
- Disposal, the final processor and small appliance safety
R-12 sample questions
Two sample questions written for this page. Try each one before you open the answer.
1. R-12 belongs to which refrigerant family?
- HFC
- HCFC
- CFC
- HFO
Show answer
C. CFC. R-12 is a CFC: it contains chlorine and no hydrogen, and its ozone depletion potential is 1.0, the same as R-11. Source: 40 CFR Part 82, Subpart A, Appendix F
2. A commercial R-12 system holds 150 pounds of refrigerant. With recovery equipment made on or after November 15, 1993, what evacuation level is required?
- 0 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
- 25 mm of mercury absolute
Show answer
B. 10 inches of mercury. EPA names R-12 as a medium-pressure refrigerant. Medium-pressure appliances need 10 inches of mercury under 200 pounds and 15 inches at 200 pounds or more. Source: 40 CFR 82.156
Want more? Practice 10 new free Type I questions every day, or get all 494 questions in the Complete Kit.
R-12 FAQ
What safety class is R-12?
R-12 is class A1: lower toxicity, no flame propagation.
What is the GWP of R-12?
10,900 (100-year global warming potential).
Does R-12 deplete ozone?
Yes. Its ozone depletion potential is 1.0, measured against R-11.
Is R-12 a high-pressure or low-pressure refrigerant?
EPA names R-12 as a medium-pressure refrigerant. With recovery equipment made on or after November 15, 1993, the required evacuation level is 10 inches of mercury under 200 lb of refrigerant, 15 inches at 200 lb or more.
Sources: 40 CFR Part 82, Subpart A, Appendix F (Class I ODP) · Montreal Protocol, Annex A (CFC ODP and GWP) · 40 CFR 82.152 (pressure definitions) · ASHRAE Standard 34 (safety classification)