EPA 608 Leak Repair Rules Explained (2026 Update)

Short version: owners of covered appliances must repair leaks when the leak rate goes over 30% (industrial process refrigeration), 20% (commercial refrigeration) or 10% (comfort cooling), generally within 30 days.

Which appliances are covered

RuleCoversIn effect
40 CFR 82.157 (ozone-depleting refrigerants)Appliances with 50 lb or more of CFC or HCFC refrigerant, such as R-22Updated in 2016; limited to ozone-depleting refrigerants since 2020
40 CFR 84.106 (AIM Act)Appliances with 15 lb or more of an HFC or listed substitute with GWP above 53. Residential and light commercial AC and heat pumps are exempt.January 1, 2026

On the Section 608 exam, only the Part 82 rules (CFC and HCFC refrigerants) are tested. The AIM Act (Part 84) rules for HFCs are not on the exam, but you must follow them on the job.

Leak rate thresholds

Appliance typeRepair when the leak rate exceeds
Industrial process refrigeration30%
Commercial refrigeration20%
Comfort cooling and other covered appliances10%

The leak rate is calculated every time refrigerant is added. That is why technicians must give the owner a record of how much refrigerant they added.

What happens after a leak is found

  1. Repair within 30 days (120 days if an industrial process shutdown is needed).
  2. Verification tests: an initial test, then a follow-up test generally within 10 days, confirm the repair held.
  3. If repairs fail: the owner must create a plan to retrofit or retire the appliance within 30 days and generally finish it within one year.
  4. Chronic leakers: appliances that lose 125% or more of their full charge in a calendar year must be reported to EPA by March 1 of the following year.
  5. Records: owners generally keep leak rate, repair and test records for 3 years.

Automatic leak detection

Under the AIM Act rules, large commercial refrigeration and industrial process appliances with a full charge of 1,500 lb or more need automatic leak detection. Systems installed from 2017 through 2025 must have it by January 1, 2027.

Sources: 40 CFR 82.157 · 40 CFR Part 84

Leak repair practice questions

From our free question bank. Try each one before you open the answer.

1. Do the leak repair rate requirements apply to small appliances?

  1. Yes, at a 10% leak rate
  2. Yes, at a 35% leak rate
  3. No, leak repair requirements apply to larger appliances
  4. Only for appliances made before 1993
Show answer

C. No, leak repair requirements apply to larger appliances. Leak repair requirements apply to larger appliances (50 pounds or more of ozone-depleting refrigerant, or 15 pounds or more of covered HFCs since 2026). Small appliances hold 5 pounds or less.

2. The Part 82 leak repair requirements apply to appliances with ozone-depleting refrigerant of at least what full charge?

  1. 5 pounds
  2. 15 pounds
  3. 50 pounds
  4. 200 pounds
Show answer

C. 50 pounds. Under 40 CFR 82.157, leak repair applies to appliances with a full charge of 50 pounds or more of class I or class II ozone-depleting refrigerant. Memory trick: Old gases, big systems: Part 82 leak repair starts at 50 pounds of ozone-depleting refrigerant.

3. What is the leak rate threshold that triggers repair for commercial refrigeration appliances?

  1. 10%
  2. 20%
  3. 30%
  4. 35%
Show answer

B. 20%. Commercial refrigeration appliances must be repaired when their leak rate exceeds 20%. The threshold is 30% for industrial process refrigeration and 10% for comfort cooling. Memory trick: 10-20-30 = Comfort, Commerce, Industry. The more a business depends on it, the higher the number.

4. What is the leak rate threshold that triggers repair for industrial process refrigeration?

  1. 10%
  2. 20%
  3. 30%
  4. 50%
Show answer

C. 30%. Industrial process refrigeration has the highest threshold, at 30%. Memory trick: 10-20-30 = Comfort, Commerce, Industry.

5. What is the leak rate threshold that triggers repair for comfort cooling appliances?

  1. 10%
  2. 20%
  3. 30%
  4. 35%
Show answer

A. 10%. Comfort cooling appliances must be repaired when the leak rate exceeds 10%. Memory trick: 10-20-30 = Comfort, Commerce, Industry. People's comfort gets the strictest limit: 10%.

Learn it step by step: Leak rates and repair deadlines on high-pressure systems (Type II lesson, 10 min, with a short check at the end).

More EPA 608 guides

Ready to test yourself?

Try free practice questions with explanations.

Start free practice