Leak rates and repair deadlines on high-pressure systems

About 10 minutes 5-question check at the end
By the end of this lesson you can:
  • Apply the 10/20/30% leak rate triggers
  • Know the repair, verification and retrofit deadlines
  • Know the record-keeping and chronic leaker rules

Which appliances are covered

On the Section 608 exam, the leak repair rules (40 CFR 82.157) apply to appliances with 50 pounds or more of ozone-depleting refrigerant, such as R-22.

On the job you must also follow the AIM Act rules for HFCs (15 lb or more, GWP above 53, since January 1, 2026). Those are not tested on the 608.

Leak rate triggers

ApplianceRepair when the leak rate exceeds
Comfort cooling10%
Commercial refrigeration20%
Industrial process refrigeration30%
Memory trick

10-20-30: Comfort, Commerce, Industry. The test likes to swap 20 and 30.

The leak rate is calculated every time refrigerant is added, which is why the technician must give the owner a record of how much was added.

Deadlines

  1. Repair within 30 days (120 days if an industrial process must shut down).
  2. Do an initial and a follow-up verification test to confirm the repair held.
  3. If the repair fails or can't be done in time, create a retrofit or retirement plan within 30 days and generally finish within one year.

Chronic leakers and records

  • An appliance that leaks 125% or more of its full charge in a calendar year must be reported to EPA by March 1 of the next year.
  • Owners generally keep leak rate, repair and test records for 3 years.

Numbers to know

50 lbPart 82 leak repair applies (ozone-depleting refrigerant)
10 / 20 / 30%Comfort / commercial / industrial
30 / 120 daysRepair deadline / with industrial shutdown
125%Chronic leaker, report by March 1
3 yearsRecord keeping

Key terms

Leak rateShare of the full charge lost per year, calculated when refrigerant is added.
Verification testTest confirming a leak repair held.
Chronically leaking applianceLoses 125% or more of its charge in a calendar year.

Exam traps

  • Swapping 20% and 30%
  • Forgetting the 120-day industrial exception
  • Applying the AIM Act numbers to a 608 exam question

Summary

  • 50 lb+ ozone-depleting: 10/20/30% triggers
  • Repair in 30 days, verify, or plan a retrofit
  • 125% in a year = chronic leaker; keep records 3 years

Quick check

Pick an answer to see the explanation.

The Part 82 leak repair requirements apply to appliances with ozone-depleting refrigerant of at least what full charge?
Answer: 50 pounds. Under 40 CFR 82.157, leak repair applies to appliances with a full charge of 50 pounds or more of class I or class II ozone-depleting refrigerant.
What is the leak rate threshold that triggers repair for commercial refrigeration appliances?
Answer: 20%. Commercial refrigeration appliances must be repaired when their leak rate exceeds 20%. The threshold is 30% for industrial process refrigeration and 10% for comfort cooling.
What is the leak rate threshold that triggers repair for industrial process refrigeration?
Answer: 30%. Industrial process refrigeration has the highest threshold, at 30%.
What is the leak rate threshold that triggers repair for comfort cooling appliances?
Answer: 10%. Comfort cooling appliances must be repaired when the leak rate exceeds 10%.
Once a leak rate above the threshold is found, how long does the owner generally have to repair the leak?
Answer: 30 days. Leaks must generally be repaired within 30 days. The window can be 120 days when an industrial process shutdown is needed.

Quick reference for this topic: EPA 608 Leak Repair Rules Explained (2026 Update)

Keep going in the Type II practice test

10 new free questions a day. Missed ones come back first.

Practice Type II

Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake