Leak rates and repair deadlines on high-pressure systems
- Apply the 10/20/30% leak rate triggers
- Know the repair, verification and retrofit deadlines
- Know the record-keeping and chronic leaker rules
Which appliances are covered
On the Section 608 exam, the leak repair rules (40 CFR 82.157) apply to appliances with 50 pounds or more of ozone-depleting refrigerant, such as R-22.
On the job you must also follow the AIM Act rules for HFCs (15 lb or more, GWP above 53, since January 1, 2026). Those are not tested on the 608.
Leak rate triggers
| Appliance | Repair when the leak rate exceeds |
|---|---|
| Comfort cooling | 10% |
| Commercial refrigeration | 20% |
| Industrial process refrigeration | 30% |
10-20-30: Comfort, Commerce, Industry. The test likes to swap 20 and 30.
The leak rate is calculated every time refrigerant is added, which is why the technician must give the owner a record of how much was added.
Deadlines
- Repair within 30 days (120 days if an industrial process must shut down).
- Do an initial and a follow-up verification test to confirm the repair held.
- If the repair fails or can't be done in time, create a retrofit or retirement plan within 30 days and generally finish within one year.
Chronic leakers and records
- An appliance that leaks 125% or more of its full charge in a calendar year must be reported to EPA by March 1 of the next year.
- Owners generally keep leak rate, repair and test records for 3 years.
Numbers to know
| 50 lb | Part 82 leak repair applies (ozone-depleting refrigerant) |
| 10 / 20 / 30% | Comfort / commercial / industrial |
| 30 / 120 days | Repair deadline / with industrial shutdown |
| 125% | Chronic leaker, report by March 1 |
| 3 years | Record keeping |
Key terms
| Leak rate | Share of the full charge lost per year, calculated when refrigerant is added. |
| Verification test | Test confirming a leak repair held. |
| Chronically leaking appliance | Loses 125% or more of its charge in a calendar year. |
Exam traps
- Swapping 20% and 30%
- Forgetting the 120-day industrial exception
- Applying the AIM Act numbers to a 608 exam question
Summary
- 50 lb+ ozone-depleting: 10/20/30% triggers
- Repair in 30 days, verify, or plan a retrofit
- 125% in a year = chronic leaker; keep records 3 years
Quick check
Pick an answer to see the explanation.
Quick reference for this topic: EPA 608 Leak Repair Rules Explained (2026 Update)
10 new free questions a day. Missed ones come back first.
Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake