EPA 608 Evacuation Requirements: The Complete Table
Before an appliance is opened or disposed of, its refrigerant must be recovered to a required level. The level depends on the type of appliance, the refrigerant charge and when the recovery equipment was made.
Appliances other than small appliances
| Appliance | Recovery equipment made before Nov 15, 1993 | Made on or after Nov 15, 1993 |
|---|---|---|
| Very high pressure | 0 in Hg | 0 in Hg |
| High pressure, less than 200 lb (for example R-22, R-410A) | 0 in Hg | 0 in Hg |
| High pressure, 200 lb or more | 4 in Hg | 10 in Hg |
| Medium pressure, less than 200 lb | 4 in Hg | 10 in Hg |
| Medium pressure, 200 lb or more | 4 in Hg | 15 in Hg |
| Low pressure | 25 mm Hg absolute | 25 mm Hg absolute |
Older study guides list separate rows for HCFC-22 and "other" high-pressure appliances. The current table in 40 CFR 82.156 has one set of rows for all high-pressure appliances, shown above.
Which refrigerants are high, medium or low pressure?
| Class | Saturation pressure at 104°F | Examples listed by EPA |
|---|---|---|
| Very high pressure | Above 355 psia | R-13, R-23, R-503 |
| High pressure | 170–355 psia | R-22, R-407C, R-410A, R-502 |
| Medium pressure | 45–170 psia | R-12, R-114, R-124, R-134a, R-500 |
| Low pressure | Below 45 psia | R-11, R-113, R-123, R-245fa |
Small appliances (5 lb or less)
| Situation | Requirement |
|---|---|
| Recovery equipment made before Nov 15, 1993 | Recover 80%, or evacuate to 4 in Hg |
| Equipment made on or after Nov 15, 1993, compressor works | Recover 90%, or evacuate to 4 in Hg |
| Equipment made on or after Nov 15, 1993, compressor does not work | Recover 80%, or evacuate to 4 in Hg |
Other rules to remember
- For a non-major repair that is not followed by an evacuation to the atmosphere, bring the appliance to 0 psig or lower before opening it (5 psig or lower for an oil change).
- Low-pressure appliances are often raised to 0 psig with controlled heat, such as hot water, before opening.
- System-dependent recovery equipment may only be used on appliances with 15 lb or less, unless it is a permanently attached pump-out unit.
- If pressure rises after recovery stops, refrigerant is still in the system: keep recovering.
Sources: 40 CFR 82.156 · 40 CFR 82.152 (definitions)
Evacuation level practice questions
From our free question bank. Try each one before you open the answer.
1. What is the main purpose of evacuating (dehydrating) a system before charging it?
- To remove air and moisture from the system
- To test the compressor oil level
- To cool the system before start-up
- To clean the condenser coil
Show answer
A. To remove air and moisture from the system. Evacuation removes air (non-condensables) and moisture. Moisture can react with refrigerant and oil to form acids and sludge, and air raises head pressure and lowers efficiency.
2. Which instrument accurately measures a deep vacuum during evacuation?
- A compound gauge on the manifold
- An electronic micron gauge
- A bubble level
- A clamp-on ammeter
Show answer
B. An electronic micron gauge. Manifold compound gauges are not precise near a full vacuum. An electronic micron gauge reads the vacuum in microns, which shows whether moisture and air have really been removed.
3. What should be done to a new recovery cylinder before its first use?
- Fill it with nitrogen to 150 psig
- Evacuate it to remove air
- Add a small amount of oil
- Nothing, it is ready to use
Show answer
B. Evacuate it to remove air. Evacuating a new or empty recovery cylinder removes air, so non-condensables are not mixed with the recovered refrigerant.
4. Using recovery equipment made BEFORE November 15, 1993, what evacuation level is required for a high-pressure appliance with 200 pounds or more of refrigerant?
- 0 inches of mercury
- 4 inches of mercury
- 10 inches of mercury
- 25 mm Hg absolute
Show answer
B. 4 inches of mercury. Under 40 CFR 82.156, high-pressure appliances with 200 pounds or more require 4 inches Hg with older recovery equipment and 10 inches Hg with equipment made on or after November 15, 1993. Memory trick: Old machines say 4. New machines: 10 for big high-pressure and small medium-pressure, 15 for big medium-pressure.
5. Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?
- 0 inches of mercury (0 psig)
- 4 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
Show answer
A. 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not. Memory trick: High pressure under 200 lb = zero: 0 inches, old or new equipment.
Learn it step by step: High-pressure recovery techniques and evacuation levels (Type II lesson, 10 min, with a short check at the end).