EPA 608 Cheat Sheet: Key Numbers and Dates (2026)
Updated November 2026 · By the EPA 608 Practice Exam team
These are the numbers that show up again and again on the EPA 608 exam. Print this page or save it to your phone.
Core
| Topic | Number or rule |
| Maximum cylinder fill | 80% of volume (liquid) |
| Recovery cylinder colors | Gray body, yellow top |
| Pressure for leak testing | Dry nitrogen with a regulator and relief valve. Never oxygen or compressed air. |
| Reclaimed refrigerant purity | AHRI Standard 700, verified by chemical analysis |
| Ozone depletion | Caused by chlorine (CFCs and HCFCs). HFCs have zero ODP. |
| A2L | Lower toxicity, lower flammability (R-32, R-454B) |
Type I – Small appliances
| Topic | Number or rule |
| Small appliance | 5 lb of refrigerant or less, factory-sealed |
| Recovery, equipment made after Nov 15, 1993, compressor works | 90% recovered, or 4 inches Hg vacuum |
| Recovery, equipment made after Nov 15, 1993, compressor does not work | 80% recovered, or 4 inches Hg vacuum |
| Open-book mail-in test | 84% to pass, does not count toward Universal |
Type II – High pressure
| Topic | Number or rule |
| Leak repair applies (ozone-depleting refrigerant) | 50 lb or more |
| Leak repair applies (HFCs, since Jan 1, 2026) | 15 lb or more, GWP above 53 (residential and light commercial AC exempt) |
| Leak rate thresholds | Industrial process 30% · Commercial refrigeration 20% · Comfort cooling 10% |
| Time to repair | 30 days (120 days if an industrial process shutdown is needed) |
| Chronic leaker report | Loses 125% or more of full charge in a calendar year |
| Non-major repair, no evacuation after | 0 psig or lower before opening (5 psig for an oil change) |
Required evacuation levels (equipment made on or after Nov 15, 1993)
| Appliance | Level |
| Very high pressure | 0 inches Hg |
| High pressure, less than 200 lb | 0 inches Hg |
| High pressure, 200 lb or more | 10 inches Hg |
| Medium pressure, less than 200 lb | 10 inches Hg |
| Medium pressure, 200 lb or more | 15 inches Hg |
| Low pressure | 25 mm Hg absolute |
Type III – Low pressure
| Topic | Number or rule |
| Rupture disc | 15 psig, on the evaporator |
| Leak test pressure | No more than 10 psig, raised with controlled hot water or heating blankets |
| Evacuation level | 25 mm Hg absolute |
| Heat oil before draining | 130°F |
| Recharging | Vapor first, then liquid, to keep water in the tubes from freezing |
AIM Act dates (job knowledge, not on the 608 exam)
| Date | Requirement |
| January 1, 2026 | HFC leak repair (15 lb, GWP above 53) takes effect |
| January 1, 2027 | Old (2018) EPA 608 question bank no longer accepted; automatic leak detection for some large systems |
| January 1, 2028 | Used disposable cylinders must go to an eligible processor or be evacuated |
Free 7-day EPA 608 email course
One short lesson a day for a week: the numbers you must know, a memory trick and 5 practice questions. We also tell you when the exam or the rules change. Unsubscribe anytime.
Always confirm details in the regulations: 40 CFR Part 82, Subpart F and 40 CFR Part 84.