R-11 on the EPA 608 Exam

R-11 is a CFC with ASHRAE safety class A1 (lower toxicity, no flame propagation), an ozone depletion potential of 1.0 and a global warming potential of 4,750. EPA Section 608 treats it as a low-pressure refrigerant.

TypeCFC
ASHRAE safety classA1 (lower toxicity, no flame propagation)
Ozone depletion potential (ODP)1.0
Global warming potential (GWP, 100-year)4,750
EPA 608 pressure classLow pressure
Where you meet itOld low-pressure centrifugal chillers. R-11 is also the reference point for ozone depletion potential.

Recovery and evacuation level for R-11

EPA names R-11 as a low-pressure refrigerant. With recovery equipment made on or after November 15, 1993, recover to 25 mm of mercury absolute before opening or disposing of the appliance.

Leak repair rules

This is an ozone-depleting refrigerant. Appliances with 50 lb or more fall under the leak repair rule in 40 CFR 82.157 (10% comfort cooling, 20% commercial refrigeration, 30% industrial process). These rates are tested on the exam.

Where R-11 shows up on the exam

Most often in Core and Type III. Practice those sections, then come back to the numbers above.

R-11 compared

Lessons that cover R-11

R-11 sample questions

Two sample questions written for this page. Try each one before you open the answer.

1. Ozone depletion potential (ODP) is measured against which refrigerant?

  1. R-11
  2. R-22
  3. R-134a
  4. Carbon dioxide
Show answer

A. R-11. R-11, a CFC, is the reference: its ODP is 1.0, and every other refrigerant's ODP is a comparison with it. Carbon dioxide is the reference for GWP, not ODP. Source: 40 CFR Part 82, Subpart A, Appendix F

2. An old centrifugal chiller uses R-11. To what level must it be evacuated before a major repair?

  1. 0 psig
  2. 4 inches of mercury
  3. 10 inches of mercury
  4. 25 mm of mercury absolute
Show answer

D. 25 mm of mercury absolute. EPA names R-11 as a low-pressure refrigerant. Low-pressure appliances must be evacuated to 25 mm of mercury absolute, no matter when the recovery equipment was made. Source: 40 CFR 82.156

Want more? Practice 10 new free Type III questions every day, or get all 494 questions in the Complete Kit.

R-11 FAQ

What safety class is R-11?

R-11 is class A1: lower toxicity, no flame propagation.

What is the GWP of R-11?

4,750 (100-year global warming potential).

Does R-11 deplete ozone?

Yes. Its ozone depletion potential is 1.0, measured against R-11.

Is R-11 a high-pressure or low-pressure refrigerant?

EPA names R-11 as a low-pressure refrigerant. With recovery equipment made on or after November 15, 1993, the required evacuation level is 25 mm of mercury absolute.

Sources: 40 CFR Part 82, Subpart A, Appendix F (Class I ODP) · Montreal Protocol, Annex A (CFC ODP and GWP) · 40 CFR 82.152 (pressure definitions) · ASHRAE Standard 34 (safety classification)