Before opening a low-pressure system for a non-major repair, how can its pressure be brought up to atmospheric?
Answer: By using controlled hot water or heat. Low-pressure systems are often below atmospheric pressure after recovery. Controlled heat, such as hot water through the tubes, raises the pressure to 0 psig so air does not rush in when the system is opened.
The four choices
- By adding compressed air
- By using controlled hot water or heat (correct)
- By opening the rupture disc
- By running the purge unit backward
Where it is taught
The lesson that covers this topic is Leak testing and recovery on low-pressure chillers, in the free Type III course.
Related Type III questions
- How should a low-pressure system be pressurized for leak testing?
- Why do leaks in a low-pressure chiller usually let air and moisture into the system?
- During a standing vacuum test on a low-pressure chiller, the pressure keeps rising. What does this indicate?