High-pressure recovery techniques and evacuation levels
By the end of this lesson you can:
- Read the evacuation level table
- Recover liquid first and speed up recovery
- Know the 0 psig rule and the 15 lb limit
Required evacuation levels
| Appliance | Recovery equipment before Nov 15, 1993 | On or after Nov 15, 1993 |
|---|---|---|
| Very high pressure | 0 in Hg | 0 in Hg |
| High pressure, under 200 lb | 0 in Hg | 0 in Hg |
| High pressure, 200 lb or more | 4 in Hg | 10 in Hg |
| Medium pressure, under 200 lb | 4 in Hg | 10 in Hg |
| Medium pressure, 200 lb or more | 4 in Hg | 15 in Hg |
Memory trick
Newer machines: "Zero, Ten-Ten-Fifteen." Older machines mostly say 4.
Recovering faster
- Recover liquid first, from the liquid line or the receiver outlet. Liquid moves much more refrigerant per minute.
- Use the push-pull method on large charges: vapor from the recovery cylinder pushes liquid out of the system.
- Recover from both the high and low side. Keep hoses short.
- Chill the recovery cylinder to lower its pressure.
- On a water-cooled condenser, circulate or drain the water so it does not freeze.
After recovery
- Wait a few minutes and watch the gauges. If pressure rises, refrigerant is still in the system: keep recovering.
- For a non-major repair not followed by evacuation to the atmosphere, bring the system to 0 psig or lower before opening (5 psig for an oil change).
- Refrigerant may be pumped down and isolated in the receiver during a non-major repair.
System-dependent recovery
Allowed only on appliances with a full charge of 15 pounds or less, unless the equipment is a permanently attached pump-out unit.
Numbers to know
| 0 / 10 / 10 / 15 in Hg | Newer equipment: high <200 · high 200+ · medium <200 · medium 200+ |
| 0 psig | Before opening for a non-major repair |
| 5 psig | Before an oil change |
| 15 lb | Maximum charge for system-dependent recovery |
Key terms
| Push-pull | Using cylinder vapor to push liquid out of a system. |
| Pump-down | Moving the charge into the receiver or condenser and isolating it. |
| Non-major repair | Repair that does not remove the compressor, condenser or evaporator. |
Exam traps
- Choosing 4 in Hg for newer equipment
- Stopping recovery when pressure is still rising
- Using system-dependent recovery on a 30 lb system
Summary
- Learn the table: newer equipment 0, 10, 10, 15
- Liquid first; push-pull for big charges
- 0 psig before a non-major repair; passive recovery only up to 15 lb
Quick check
Pick an answer to see the explanation.
Using recovery equipment made BEFORE November 15, 1993, what evacuation level is required for a high-pressure appliance with 200 pounds or more of refrigerant?
Answer: 4 inches of mercury. Under 40 CFR 82.156, high-pressure appliances with 200 pounds or more require 4 inches Hg with older recovery equipment and 10 inches Hg with equipment made on or after November 15, 1993.
Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?
Answer: 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not.
What evacuation level is required for a very high-pressure appliance?
Answer: 0 inches of mercury. Very high-pressure appliances must be evacuated to 0 inches of mercury, regardless of when the recovery equipment was made.
Why should you recover liquid refrigerant first when possible?
Answer: Liquid recovery is faster and removes more refrigerant quickly. Removing liquid first moves the bulk of the charge much faster than vapor recovery alone. Finish by recovering the remaining vapor.
For a non-major repair that is not followed by an evacuation to the atmosphere, to what pressure must the appliance be evacuated before opening?
Answer: 0 psig. For non-major repairs that are not followed by an evacuation to the atmosphere, medium-, high- and very high-pressure appliances must be brought to 0 psig or lower before they are opened. For an oil change the limit is 5 psig.
Quick reference for this topic: EPA 608 Evacuation Requirements: The Complete Table
Keep going in the Type II practice test
Practice Type II10 new free questions a day. Missed ones come back first.
Previous lessonLeak rates and repair deadlines on high-pressure systemsNext lessonFinding leaks and diagnosing high-pressure systems
Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake