R-290 on the EPA 608 Exam
R-290 is a hydrocarbon (propane) with ASHRAE safety class A3 (lower toxicity, higher flammability), an ozone depletion potential of 0 and a global warming potential of 3.3.
| Type | hydrocarbon (propane) |
| ASHRAE safety class | A3 (lower toxicity, higher flammability) |
| Ozone depletion potential (ODP) | 0 |
| Global warming potential (GWP, 100-year) | 3.3 (IPCC 2007 (AR4)) |
| EPA 608 pressure class | Not named in EPA's definitions |
| Where you meet it | Small self-contained commercial refrigeration and some room air conditioners. |
Recovery and evacuation level for R-290
EPA's pressure definitions do not name R-290. The class depends on its saturation pressure at 104°F (40 CFR 82.152), so read it from a pressure-temperature chart and then use the evacuation table.
Leak repair rules
It does not deplete ozone and its GWP is not above 53, so neither leak repair threshold applies. Follow EPA's rules for the specific use before releasing or recovering it.
Where R-290 shows up on the exam
Most often in Core. Practice those sections, then come back to the numbers above.
R-290 compared
- R-290 vs R-600a: safety class A3 vs A3, GWP 3.3 vs 1, ODP 0 vs 0.
- R-290 vs R-32: safety class A3 vs A2L, GWP 3.3 vs 675, ODP 0 vs 0.
Lessons that cover R-290
- Disposal, the final processor and small appliance safety
- Refrigerant safety classes and hazards on the job
R-290 sample questions
Two sample questions written for this page. Try each one before you open the answer.
1. What is the ASHRAE safety class of R-290 (propane)?
- A1
- A2L
- A3
- B1
Show answer
C. A3. R-290 is class A3: lower toxicity, higher flammability. The letter shows toxicity (A is lower) and the number shows flammability (3 is the highest class). Source: ASHRAE Standard 34
2. Why is R-290 used in some new appliances even though it is highly flammable?
- It does not deplete ozone and its global warming potential is very low
- It runs in a deep vacuum
- It contains chlorine
- It will not burn in small amounts
Show answer
A. It does not deplete ozone and its global warming potential is very low. R-290 has an ODP of 0, and EPA's table lists its GWP as 3.3, compared with 2,088 for R-410A. The trade-off is flammability, so it is used in small charges with tools rated for flammable refrigerants. Source: EPA Technology Transitions GWP reference table
Want more? Practice 10 new free Core questions every day, or get all 494 questions in the Complete Kit.
R-290 FAQ
What safety class is R-290?
R-290 is class A3: lower toxicity, higher flammability.
What is the GWP of R-290?
3.3 (100-year global warming potential).
Does R-290 deplete ozone?
No. Its ozone depletion potential is 0.
Sources: EPA Technology Transitions GWP reference table (40 CFR 84.64) · ASHRAE Standard 34 (safety classification)