R-22 on the EPA 608 Exam
R-22 is an HCFC with ASHRAE safety class A1 (lower toxicity, no flame propagation), an ozone depletion potential of 0.055 and a global warming potential of 1,810. EPA Section 608 treats it as a high-pressure refrigerant.
| Type | HCFC |
| ASHRAE safety class | A1 (lower toxicity, no flame propagation) |
| Ozone depletion potential (ODP) | 0.055 |
| Global warming potential (GWP, 100-year) | 1,810 |
| EPA 608 pressure class | High pressure |
| Where you meet it | Older residential and commercial air conditioners and refrigeration. |
Recovery and evacuation level for R-22
EPA names R-22 as a high-pressure refrigerant. With recovery equipment made on or after November 15, 1993, recover to 0 inches of mercury under 200 lb of refrigerant, 10 inches at 200 lb or more before opening or disposing of the appliance.
Leak repair rules
This is an ozone-depleting refrigerant. Appliances with 50 lb or more fall under the leak repair rule in 40 CFR 82.157 (10% comfort cooling, 20% commercial refrigeration, 30% industrial process). These rates are tested on the exam.
Where R-22 shows up on the exam
Most often in Core and Type II. Practice those sections, then come back to the numbers above.
R-22 compared
- R-22 vs R-410A: safety class A1 vs A1, GWP 1,810 vs 2,088, ODP 0.055 vs 0.
- R-22 vs R-123: safety class A1 vs B1, GWP 1,810 vs 77, ODP 0.055 vs 0.02.
Lessons that cover R-22
R-22 practice questions
From our free question bank.
1. Which of these refrigerants is an HCFC?
- R-12
- R-22
- R-134a
- R-410A
Show answer
B. R-22. R-22 (chlorodifluoromethane) is an HCFC. R-12 is a CFC, while R-134a and R-410A are HFCs. Memory trick: Read the letters: CFC = no hydrogen (worst), HCFC = hydrogen added (less harm), HFC = no chlorine (zero ozone harm).
2. What can happen when refrigerants such as R-22 are exposed to an open flame or very hot surface?
- They become harmless water vapor
- They can decompose into toxic gases such as phosgene and acids
- They form pure oxygen
- Nothing happens
Show answer
B. They can decompose into toxic gases such as phosgene and acids. High heat breaks many refrigerants down into toxic and corrosive products, including hydrochloric acid, hydrofluoric acid and phosgene. Ventilate the area and avoid flames near leaks.
3. Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?
- 0 inches of mercury (0 psig)
- 4 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
Show answer
A. 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not. Memory trick: High pressure under 200 lb = zero: 0 inches, old or new equipment.
4. When leak testing with nitrogen, is it allowed to add a small amount of R-22 as a trace gas?
- Yes, a trace amount of refrigerant mixed with nitrogen may be used for leak detection
- No, refrigerant may never be released for any reason
- Yes, but only R-12
- Only if the system holds more than 500 pounds
Show answer
A. Yes, a trace amount of refrigerant mixed with nitrogen may be used for leak detection. EPA allows a small amount of refrigerant to be used as a trace gas with nitrogen for leak testing. Releasing that mixture is not treated as knowing venting of refrigerant.
5. How do R-410A operating pressures compare with R-22?
- They are significantly higher
- They are about the same
- They are much lower
- They are below atmospheric pressure
Show answer
A. They are significantly higher. R-410A runs at much higher pressures than R-22. Gauges, hoses and recovery equipment must be rated for these pressures.
Want more? Practice 10 new free Type II questions every day, or get all 494 questions in the Complete Kit.
R-22 FAQ
What safety class is R-22?
R-22 is class A1: lower toxicity, no flame propagation.
What is the GWP of R-22?
1,810 (100-year global warming potential).
Does R-22 deplete ozone?
Yes. Its ozone depletion potential is 0.055, measured against R-11.
Is R-22 a high-pressure or low-pressure refrigerant?
EPA names R-22 as a high-pressure refrigerant. With recovery equipment made on or after November 15, 1993, the required evacuation level is 0 inches of mercury under 200 lb of refrigerant, 10 inches at 200 lb or more.
Sources: 40 CFR Part 82, Subpart A, Appendix B (Class II ODP) · Montreal Protocol, Annex C (HCFC ODP and GWP) · 40 CFR 82.152 (pressure definitions) · ASHRAE Standard 34 (safety classification)