Why is liquid not added first when charging a low-pressure chiller from a deep vacuum?
Answer: The liquid would boil rapidly, chill the tubes and could freeze the water inside. At very low pressure, liquid refrigerant flashes to vapor and pulls the temperature down. Vapor first raises the pressure above the point where water in the tubes could freeze.
The four choices
- Liquid is more expensive
- The liquid would boil rapidly, chill the tubes and could freeze the water inside (correct)
- Liquid cannot pass the expansion device
- Liquid damages the purge unit
Where it is taught
This question is part of the check at the end of the lesson Recharging chillers and machinery room safety, in the free Type III course.