Why can't you simply use bubble solution on a low-pressure chiller while it is in a vacuum?
Answer: Bubbles do not form, because air is being pulled in rather than refrigerant pushed out. Under vacuum, a leak pulls air inward, so no bubbles form. Raise the pressure slightly with controlled heat (no more than 10 psig) before testing.
The four choices
- Bubbles do not form, because air is being pulled in rather than refrigerant pushed out (correct)
- Bubble solution freezes
- It damages the purge unit
- It is illegal
Related Type III questions
- Why do leaks in a low-pressure chiller usually let air and moisture into the system?
- Why is moisture in a low-pressure chiller harmful?
- What is the purpose of a purge unit on a low-pressure chiller?