Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?

Answer: 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not.

The four choices

  1. 0 inches of mercury (0 psig) (correct)
  2. 4 inches of mercury
  3. 10 inches of mercury
  4. 15 inches of mercury

Memory trick: High pressure under 200 lb = zero: 0 inches, old or new equipment.

Where it is taught

This question is part of the check at the end of the lesson High-pressure recovery techniques and evacuation levels, in the free Type II course.