EPA 608 Type III Practice Test (2026)
Type III covers low-pressure appliances, mainly centrifugal chillers that use refrigerants such as R-123 and R-1233zd(E). Answer each question to see the explanation right away. You get a new set of 10 every day, and questions you miss come back first.
New to this section? Read the Type III course first: 3 short lessons, about 25 minutes.
What the Type III section covers
- Why low-pressure systems pull air in
- Purge units
- Rupture discs (15 psig)
- Leak testing with controlled heat (10 psig max)
- Recovery to 25 mm Hg absolute
- Heating oil to 130°F
- Recharging with vapor first
- Protecting chiller tubes from freezing
The real exam has 25 questions in this section and you need 18 correct (70%) to pass. Ready for a full test? Take the free mock exam.
10 sample EPA 608 Type III questions with answers
The same questions as plain text, for when you want to read rather than click.
1. Which of these is a low-pressure refrigerant?
- R-410A
- R-22
- R-123
- R-404A
Show answer
C. R-123. R-123 is a low-pressure refrigerant used in centrifugal chillers. R-1233zd(E) and R-11 are other low-pressure refrigerants.
2. Why do leaks in a low-pressure chiller usually let air and moisture into the system?
- Because the evaporator operates below atmospheric pressure
- Because low-pressure refrigerants are lighter than air
- Because the purge unit pulls air in
- Because the condenser is always open
Show answer
A. Because the evaporator operates below atmospheric pressure. Parts of a low-pressure system run in a vacuum. A leak there lets air and moisture in instead of letting refrigerant out. Memory trick: High pushes out, low pulls in: low-pressure chillers suck air IN through leaks.
3. What is the purpose of a purge unit on a low-pressure chiller?
- To add refrigerant
- To remove non-condensables such as air from the system
- To drain the oil
- To cool the motor
Show answer
B. To remove non-condensables such as air from the system. The purge unit pulls air and other non-condensables out of the condenser. High-efficiency purge units release very little refrigerant while doing this. Memory trick: Purge = 'push out the party crashers': it removes air from the top of the condenser.
4. At what pressure does the rupture disc on a low-pressure chiller evaporator typically open?
- 5 psig
- 15 psig
- 50 psig
- 150 psig
Show answer
B. 15 psig. The rupture disc on a low-pressure chiller evaporator is typically set at 15 psig to protect the shell from overpressure. Memory trick: Ten to Test, Fifteen to Flip: leak test at 10 psig max, rupture disc bursts at 15.
5. How should a low-pressure system be pressurized for leak testing?
- With compressed air at 100 psig
- By using controlled hot water or heating blankets, to no more than 10 psig
- With oxygen
- With R-22 at full cylinder pressure
Show answer
B. By using controlled hot water or heating blankets, to no more than 10 psig. Raise the system pressure with controlled hot water or heating blankets, keeping it at no more than 10 psig so the rupture disc does not open. Memory trick: Ten to Test, Fifteen to Flip: leak test at 10 psig max, rupture disc bursts at 15.
6. When recovering refrigerant from a low-pressure chiller, what should be removed first?
- Vapor
- Liquid
- Oil
- Water
Show answer
B. Liquid. Remove the liquid first, then recover the remaining vapor. Removing liquid first is much faster.
7. To what level must a low-pressure appliance be evacuated during recovery?
- 0 psig
- 10 inches of mercury
- 25 mm Hg absolute
- 500 microns
Show answer
C. 25 mm Hg absolute. Low-pressure appliances must be evacuated to 25 mm Hg absolute, regardless of when the recovery equipment was made. Memory trick: Low pressure = 25 mm Hg absolute, no matter how old the recovery machine is.
8. While recovering refrigerant from a chiller, what should be done with the water in the tubes?
- Circulate it to prevent freezing
- Shut it off immediately
- Heat it above 200°F
- Add refrigerant oil to it
Show answer
A. Circulate it to prevent freezing. As refrigerant is removed, the temperature in the shell can drop below freezing. Circulating water through the tubes, or draining it, prevents freezing and tube damage. Memory trick: Moving water doesn't freeze: keep the water flowing (or drained) while you pull refrigerant out.
9. To what temperature should oil be heated before it is drained from a low-pressure chiller?
- 32°F
- 70°F
- 130°F
- 212°F
Show answer
C. 130°F. Heating the oil to about 130°F drives out refrigerant dissolved in it, so less refrigerant leaves the system with the oil. Memory trick: Heat the oil to 130°F to cook the refrigerant out of it.
10. When recharging a low-pressure chiller after evacuation, what should be introduced first?
- Liquid refrigerant
- Refrigerant vapor
- Nitrogen
- Water
Show answer
B. Refrigerant vapor. Charge vapor first. Liquid added to a deep vacuum would boil instantly, drop the temperature and could freeze the water in the tubes. Memory trick: Vapor first, then liquid: no frozen tubes.
Type III section FAQ
At what pressure does a low-pressure chiller's rupture disc open?
About 15 psig. That is why a low-pressure chiller is leak tested at no more than 10 psig.
What evacuation level applies to low-pressure appliances?
25 mm of mercury absolute, no matter when the recovery equipment was made.
Why charge a low-pressure chiller with vapor first?
Liquid entering a deep vacuum can freeze the water in the tubes. Charge vapor until the saturation temperature is above 32°F, then switch to liquid.
En español: Práctica EPA 608 Tipo III en español
Prefer to read? All free Type III questions with answers, one page each.
More practice: Core · Type I · Type II · EPA 608 cheat sheet