EPA 608 Type II Practice Test (2026)
Type II covers high-pressure and very high-pressure appliances, such as residential split systems, rooftop units and commercial refrigeration. Answer each question to see the explanation right away. You get a new set of 10 every day, and questions you miss come back first.
New to this section? Read the Type II course first: 4 short lessons, about 37 minutes.
What the Type II section covers
- Leak repair thresholds (10%, 20%, 30%)
- The 2026 HFC leak repair rule (15 lb and GWP above 53)
- Chronically leaking appliances
- Required evacuation levels
- Liquid vs vapor recovery
- Leak detection methods
- Non-condensables and head pressure
- R-410A, R-454B and R-32
The real exam has 25 questions in this section and you need 18 correct (70%) to pass. Ready for a full test? Take the free mock exam.
10 sample EPA 608 Type II questions with answers
The same questions as plain text, for when you want to read rather than click.
1. Which of these is a high-pressure refrigerant?
- R-11
- R-123
- R-410A
- R-1233zd(E)
Show answer
C. R-410A. R-410A and R-22 are high-pressure refrigerants used in comfort cooling and refrigeration. R-11, R-123 and R-1233zd(E) are low-pressure refrigerants used in centrifugal chillers.
2. The Part 82 leak repair requirements apply to appliances with ozone-depleting refrigerant of at least what full charge?
- 5 pounds
- 15 pounds
- 50 pounds
- 200 pounds
Show answer
C. 50 pounds. Under 40 CFR 82.157, leak repair applies to appliances with a full charge of 50 pounds or more of class I or class II ozone-depleting refrigerant. Memory trick: Old gases, big systems: Part 82 leak repair starts at 50 pounds of ozone-depleting refrigerant.
3. What is the leak rate threshold that triggers repair for commercial refrigeration appliances?
- 10%
- 20%
- 30%
- 35%
Show answer
B. 20%. Commercial refrigeration appliances must be repaired when their leak rate exceeds 20%. The threshold is 30% for industrial process refrigeration and 10% for comfort cooling. Memory trick: 10-20-30 = Comfort, Commerce, Industry. The more a business depends on it, the higher the number.
4. What is the leak rate threshold that triggers repair for industrial process refrigeration?
- 10%
- 20%
- 30%
- 50%
Show answer
C. 30%. Industrial process refrigeration has the highest threshold, at 30%. Memory trick: 10-20-30 = Comfort, Commerce, Industry.
5. What is the leak rate threshold that triggers repair for comfort cooling appliances?
- 10%
- 20%
- 30%
- 35%
Show answer
A. 10%. Comfort cooling appliances must be repaired when the leak rate exceeds 10%. Memory trick: 10-20-30 = Comfort, Commerce, Industry. People's comfort gets the strictest limit: 10%.
6. Once a leak rate above the threshold is found, how long does the owner generally have to repair the leak?
- 7 days
- 30 days
- 90 days
- 1 year
Show answer
B. 30 days. Leaks must generally be repaired within 30 days. The window can be 120 days when an industrial process shutdown is needed. Memory trick: 30 days to fix it, 120 if the plant has to shut down.
7. Using recovery equipment made BEFORE November 15, 1993, what evacuation level is required for a high-pressure appliance with 200 pounds or more of refrigerant?
- 0 inches of mercury
- 4 inches of mercury
- 10 inches of mercury
- 25 mm Hg absolute
Show answer
B. 4 inches of mercury. Under 40 CFR 82.156, high-pressure appliances with 200 pounds or more require 4 inches Hg with older recovery equipment and 10 inches Hg with equipment made on or after November 15, 1993. Memory trick: Old machines say 4. New machines: 10 for big high-pressure and small medium-pressure, 15 for big medium-pressure.
8. Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?
- 0 inches of mercury (0 psig)
- 4 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
Show answer
A. 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not. Memory trick: High pressure under 200 lb = zero: 0 inches, old or new equipment.
9. What evacuation level is required for a very high-pressure appliance?
- 0 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
- 25 mm Hg absolute
Show answer
A. 0 inches of mercury. Very high-pressure appliances must be evacuated to 0 inches of mercury, regardless of when the recovery equipment was made. Memory trick: Very high pressure = zero, always.
10. An appliance that leaks 125% or more of its full charge in a calendar year must be handled how?
- Nothing special is required
- The owner must report it to EPA as a chronically leaking appliance
- The appliance must be scrapped immediately
- The technician loses certification
Show answer
B. The owner must report it to EPA as a chronically leaking appliance. Appliances that lose 125% or more of their full charge in a calendar year are chronically leaking. The owner must report them to EPA by March 1 of the following year. Memory trick: Leaked more than it holds (125%)? Report it to EPA by March 1.
Type II section FAQ
What leak rates trigger a repair on the Type II test?
For appliances with 50 pounds or more of CFC or HCFC refrigerant: 10% for comfort cooling, 20% for commercial refrigeration and 30% for industrial process refrigeration.
What evacuation level applies to a high-pressure appliance?
With recovery equipment made on or after November 15, 1993: 0 inches of mercury under 200 pounds of refrigerant, and 10 inches at 200 pounds or more.
How many Type II questions do I need to get right?
18 of 25 (70%), plus a passing score on Core.
En español: Práctica EPA 608 Tipo II en español
Prefer to read? All free Type II questions with answers, one page each.