Leak testing with nitrogen, then evacuation and dehydration
By the end of this lesson you can:
- Pressurize a system for a leak test safely
- Explain why and how a system is evacuated
- Read a vacuum decay test
Pressurizing for a leak test
- Use dry nitrogen through a pressure regulator with a relief valve. A full nitrogen cylinder can hold more than 2,000 psig.
- Never use oxygen or compressed air. Oxygen and oil under pressure can explode.
- A trace amount of refrigerant (for example R-22) may be mixed with nitrogen so an electronic detector can find the leak.
- Never go above the test pressure on the equipment nameplate.
Why evacuate
Evacuation pulls a deep vacuum to remove air and moisture. At very low pressure, water boils at room temperature, turns to vapor and is pulled out by the pump. Moisture left inside forms acids and sludge; air raises head pressure.
Measuring the vacuum
| Item | Value |
|---|---|
| Perfect vacuum on a compound gauge, sea level | About 29.92 in Hg |
| Atmospheric pressure, sea level | About 14.7 psia (0 psig) |
| Common target after repairs | About 500 microns, unless the manufacturer says otherwise |
A compound gauge is too coarse for a deep vacuum. Use a micron gauge (electronic vacuum gauge).
Reading a decay test
Isolate the pump and watch the micron gauge. A rise that levels off means moisture is still boiling off: keep evacuating. A rise that keeps climbing means a leak.
Good practice
- Use short, large-diameter hoses and remove Schrader cores to speed evacuation.
- Change vacuum pump oil often; wet oil cannot pull a deep vacuum.
- Replace the filter-drier whenever the system has been opened.
Numbers to know
| 29.92 in Hg | Perfect vacuum at sea level |
| 14.7 psia | Atmospheric pressure at sea level |
| ~500 microns | Common evacuation target |
| psia = psig + 14.7 | Absolute vs gauge pressure |
Key terms
| Micron gauge | Electronic gauge that reads deep vacuum. |
| Decay test | Watching the vacuum hold after isolating the pump. |
| psig | Pressure above atmosphere. |
| psia | Pressure above a perfect vacuum. |
Exam traps
- Choosing compressed air or oxygen for a leak test
- Trusting a compound gauge for deep vacuum
- Reading a leveling-off rise as a leak
Summary
- Leak test with dry nitrogen, regulator and relief valve
- Evacuate to remove air and moisture; measure with a micron gauge
- Levels off = moisture; keeps climbing = leak
Quick check
Pick an answer to see the explanation.
Which gas should be used to pressurize a system for a leak test?
Answer: Dry nitrogen, through a pressure regulator and relief valve. Use dry nitrogen with a pressure regulator and a relief valve. Never use oxygen or compressed air, which can explode when mixed with compressor oil under pressure.
Why must oxygen never be used to pressurize a refrigeration system?
Answer: It can cause an explosion when it contacts compressor oil under pressure. Oxygen and oil under pressure can ignite violently. The same is true of compressed air, which is about 21% oxygen.
What is the main purpose of evacuating (dehydrating) a system before charging it?
Answer: To remove air and moisture from the system. Evacuation removes air (non-condensables) and moisture. Moisture can react with refrigerant and oil to form acids and sludge, and air raises head pressure and lowers efficiency.
Which instrument accurately measures a deep vacuum during evacuation?
Answer: An electronic micron gauge. Manifold compound gauges are not precise near a full vacuum. An electronic micron gauge reads the vacuum in microns, which shows whether moisture and air have really been removed.
After reaching your target vacuum, you isolate the pump and the micron reading rises quickly and keeps climbing. What does this usually mean?
Answer: There is a leak in the system or hoses. A reading that keeps climbing without leveling off points to a leak. A rise that levels off usually means moisture is still boiling off.
Keep going in the Core practice test
Practice Core10 new free questions a day. Missed ones come back first.
Previous lessonHandling cylinders and recovery equipmentNext lessonRefrigerant safety classes and hazards on the job
Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake