Finding leaks and diagnosing high-pressure systems
By the end of this lesson you can:
- Pick the right leak detection method
- Pressure test with nitrogen safely
- Read superheat, subcooling and non-condensable symptoms
Signs of a leak
- Oil traces or stains on fittings and coils are the most common visible sign.
- Start a leak search with a general check of the whole system, then pinpoint.
- Pinpoint a small leak with soap bubbles or an electronic detector.
Detection methods
| Method | Note |
|---|---|
| Bubble solution | Pinpoints the exact spot |
| Electronic detector | Must be rated for the refrigerant (A2L-rated for R-32, R-454B) |
| Ultrasonic detector | Listens for the high-frequency sound of escaping gas |
| Halide torch | Only detects chlorine refrigerants. Never near A2L or A3 |
Nitrogen pressure test
- Use a regulator and relief valve; never exceed the test pressure on the nameplate.
- Flow a little dry nitrogen through tubing while brazing to prevent oxide scale inside.
- A standing test whose pressure drops while temperature stays the same means a leak.
Reading the system
| Reading | Usually means |
|---|---|
| Low suction pressure and low subcooling (TXV system) | Undercharge |
| High subcooling and high head pressure | Overcharge |
| High head pressure that won't come down | Non-condensables (air) |
| Ice at the metering device off and on | Moisture in the system |
Memory trick
Fixed metering device: check charge by superheat. TXV: check by subcooling.
Numbers to know
| Nameplate | Maximum nitrogen test pressure |
Key terms
| Ultrasonic leak detector | Detects the sound of escaping gas. |
| Non-condensables | Air and other gases that raise head pressure. |
| TXV | Thermostatic expansion valve. |
Exam traps
- Using a halide torch on an HFC or A2L system
- Testing with nitrogen and no regulator
- Charging a TXV system by superheat
Summary
- Oil stains are the classic leak sign
- Nitrogen test: regulator, relief valve, nameplate pressure
- Fixed device by superheat, TXV by subcooling
Quick check
Pick an answer to see the explanation.
What is a common visible sign of a refrigerant leak on a high-pressure system?
Answer: Oil stains or traces at joints and fittings. Refrigerant carries oil as it escapes, so oily residue around fittings, joints and valves often marks a leak.
What is the best way to pinpoint the exact location of a small leak?
Answer: Apply bubble solution to the suspected joint. An electronic detector can find the general area, and a bubble solution applied to a suspected joint shows exactly where the leak is.
When leak testing with nitrogen, is it allowed to add a small amount of R-22 as a trace gas?
Answer: Yes, a trace amount of refrigerant mixed with nitrogen may be used for leak detection. EPA allows a small amount of refrigerant to be used as a trace gas with nitrogen for leak testing. Releasing that mixture is not treated as knowing venting of refrigerant.
What is a common symptom of non-condensables (air) in a high-pressure system?
Answer: Higher than normal head (discharge) pressure. Air collects in the condenser and cannot condense, which raises head pressure, increases power use and reduces capacity.
Which type of leak detector only works with refrigerants that contain chlorine, such as CFCs and HCFCs?
Answer: A halide torch. A halide torch reacts to chlorine, so it cannot detect HFCs. Open flames are also dangerous around flammable refrigerants.
Keep going in the Type II practice test
Practice Type II10 new free questions a day. Missed ones come back first.
Previous lessonHigh-pressure recovery techniques and evacuation levelsNext lessonHigh-pressure refrigerants and pressure classes