How low-pressure chillers work
By the end of this lesson you can:
- Explain why low-pressure leaks pull air in
- Describe the purge unit and the rupture disc
- Name the common low-pressure refrigerants
Running in a vacuum
A low-pressure appliance uses a refrigerant with a saturation pressure below 45 psia at 104°F. Centrifugal chillers using R-123 run with the evaporator below atmospheric pressure. So a leak does not blow refrigerant out: it pulls air and moisture in.
Memory trick
High pushes out, low pulls in.
The purge unit
- Air and other non-condensables collect at the top of the condenser. The purge unit removes them and returns refrigerant to the system.
- Non-condensables raise condenser pressure and waste energy; moisture forms acid.
- A purge unit that runs more and more often means air is getting in: there is a leak. Track purge run time.
- High-efficiency purge units release very little refrigerant with the air.
The rupture disc
The rupture disc on the evaporator bursts at 15 psig to protect the chiller from overpressure. After an overpressure event, check and replace it.
Refrigerants
| Refrigerant | Family | Safety class |
|---|---|---|
| R-11 | CFC, older chillers | A1 |
| R-123 | HCFC, new supply ends with the 2030 HCFC phaseout | B1 |
| R-1233zd(E) | HFO, low-GWP replacement | A1 |
| R-514A | HFO-based blend | B1 |
Numbers to know
| 45 psia | Low-pressure boundary at 104°F |
| 15 psig | Rupture disc on the evaporator |
| 2030 | HCFC phaseout complete; new R-123 ends |
Key terms
| Purge unit | Removes non-condensables from the condenser. |
| Rupture disc | Burst disc on the evaporator, 15 psig. |
| Non-condensables | Air and gases that don't condense. |
Exam traps
- Putting the purge unit on the evaporator
- Putting the rupture disc on the condenser
- Calling R-134a a low-pressure refrigerant
Summary
- Low-pressure chillers run in a vacuum, so leaks pull air in
- Purge unit on the condenser; more purging = a leak
- Rupture disc on the evaporator at 15 psig
Quick check
Pick an answer to see the explanation.
Which of these is a low-pressure refrigerant?
Answer: R-123. R-123 is a low-pressure refrigerant used in centrifugal chillers. R-1233zd(E) and R-11 are other low-pressure refrigerants.
Why do leaks in a low-pressure chiller usually let air and moisture into the system?
Answer: Because the evaporator operates below atmospheric pressure. Parts of a low-pressure system run in a vacuum. A leak there lets air and moisture in instead of letting refrigerant out.
What is the purpose of a purge unit on a low-pressure chiller?
Answer: To remove non-condensables such as air from the system. The purge unit pulls air and other non-condensables out of the condenser. High-efficiency purge units release very little refrigerant while doing this.
At what pressure does the rupture disc on a low-pressure chiller evaporator typically open?
Answer: 15 psig. The rupture disc on a low-pressure chiller evaporator is typically set at 15 psig to protect the shell from overpressure.
A purge unit that runs much more often than normal most likely means what?
Answer: Air is leaking into the system. Frequent purge operation means non-condensables are entering the system, usually through a leak on the low-pressure side. Find and fix the leak.
Keep going in the Type III practice test
Practice Type III10 new free questions a day. Missed ones come back first.
Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake