Courses / Type II / Lesson 4 of 4

High-pressure refrigerants and pressure classes

About 8 minutes 5-question check at the end
By the end of this lesson you can:
  • Classify refrigerants as very high, high or medium pressure
  • Handle R-410A and the A2L replacements correctly
  • Know where R-22 comes from now

Pressure classes

ClassSaturation pressure at 104°FExamples
Very highAbove 355 psiaR-13, R-23, R-503
High170 to 355 psiaR-22, R-407C, R-410A, R-502
Medium45 to 170 psiaR-12, R-134a, R-124, R-500

R-410A

  • Runs at much higher pressure than R-22, so gauges, hoses and recovery cylinders must be rated for it (400 psig service rating for cylinders).
  • It is a zeotropic blend: charge as liquid.
  • New residential AC made since January 1, 2025 can no longer use it because its GWP is above 700.

The replacements

R-410AR-454BR-32
Safety classA1A2LA2L
Make-upR-32 + R-125R-32 + R-1234yfSingle component
GWPAbout 2,088About 466About 675
  • Never convert an R-410A system to R-454B in the field unless the manufacturer approves it.
  • Before brazing on an A2L system, recover the refrigerant and purge with nitrogen.
  • Leak sensors in many R-454B indoor units start the blower and stop the compressor when they detect refrigerant.

R-22 today

Since January 1, 2020, no new R-22 is produced or imported for servicing. Service uses recovered, recycled or reclaimed R-22, or stock made before 2020.

Numbers to know

355 / 170 / 45 psiaBoundaries between very high, high, medium and low pressure at 104°F
400 psigCylinder rating for R-410A
Jan 1, 2020End of new R-22 for servicing

Key terms

Very high-pressure applianceRefrigerant above 355 psia at 104°F.
High-pressure appliance170–355 psia at 104°F.
Medium-pressure appliance45–170 psia at 104°F.

Exam traps

  • Calling R-134a a high-pressure refrigerant. It is medium
  • Charging R-410A or R-454B as vapor
  • Dropping R-454B into an R-410A system

Summary

  • R-22 and R-410A are high pressure; R-134a is medium
  • R-454B and R-32 are A2L replacements for R-410A
  • New R-22 ended in 2020

Quick check

Pick an answer to see the explanation.

Which of these is a high-pressure refrigerant?
Answer: R-410A. R-410A and R-22 are high-pressure refrigerants used in comfort cooling and refrigeration. R-11, R-123 and R-1233zd(E) are low-pressure refrigerants used in centrifugal chillers.
How do R-410A operating pressures compare with R-22?
Answer: They are significantly higher. R-410A runs at much higher pressures than R-22. Gauges, hoses and recovery equipment must be rated for these pressures.
What is the ASHRAE safety classification of R-454B?
Answer: A2L. R-454B is classified A2L: lower toxicity and lower flammability. Technicians need tools, recovery equipment and procedures rated for A2L refrigerants.
Which of these refrigerants is used in very high-pressure appliances?
Answer: R-23. Very high-pressure refrigerants such as R-13, R-23 and R-503 are used in low-temperature applications like ultra-low freezers.
Which of these is a high-pressure refrigerant used in comfort cooling?
Answer: R-22. R-22 is a high-pressure HCFC refrigerant. R-11, R-113 and R-123 are low-pressure refrigerants.

Quick reference for this topic: R-454B vs R-410A vs R-32: What Technicians Need to Know

Keep going in the Type II practice test

10 new free questions a day. Missed ones come back first.

Practice Type II

Written by the EPA 608 Practice Exam team from 40 CFR Part 82, Subpart F. How we check it · Report a mistake