Courses / Type III / Lesson 3 of 3

Recharging chillers and machinery room safety

About 7 minutes 5-question check at the end
By the end of this lesson you can:
  • Recharge a chiller from a vacuum without freezing tubes
  • Know the ASHRAE 15 machinery room requirements
  • Apply the leak repair rules to chillers

Recharging from a vacuum

Add vapor first. Liquid added to a chiller in a deep vacuum boils instantly and can freeze the water in the tubes. Once the saturation temperature in the evaporator is above 32°F, switch to liquid.

Memory trick

Vapor first, no frozen tubes.

Tube leaks

The refrigerant side is usually at lower pressure than the water side, so a leaking tube lets water into the refrigerant. That brings moisture and acid. Refrigerant from a chiller with a known tube leak should be treated as contaminated.

Machinery rooms

  • ASHRAE Standard 15 requires a refrigerant detector that sounds an alarm and starts mechanical ventilation.
  • Refrigerant vapor is heavier than air and collects near the floor.
  • If the alarm sounds after a large release, leave the room and do not re-enter without proper breathing protection.

Leak repair rules

Chillers with 50 lb or more of ozone-depleting refrigerant follow the same rules as Type II: 10% for comfort cooling, 30% for industrial process, repair within 30 days, and report a chronic leaker (125% in a year) by March 1.

Numbers to know

32°FSaturation temperature to reach before charging liquid
10% / 30%Leak triggers: comfort cooling / industrial process chillers

Key terms

ASHRAE 15Safety standard for refrigeration systems and machinery rooms.
Refrigerant monitorDetector that alarms and starts ventilation.

Exam traps

  • Charging liquid first into a chiller in deep vacuum
  • Thinking a tube leak lets refrigerant into the water

Summary

  • Vapor first until above 32°F, then liquid
  • Tube leaks put water into the refrigerant
  • Machinery rooms need detectors, alarms and ventilation

Quick check

Pick an answer to see the explanation.

When recharging a low-pressure chiller after evacuation, what should be introduced first?
Answer: Refrigerant vapor. Charge vapor first. Liquid added to a deep vacuum would boil instantly, drop the temperature and could freeze the water in the tubes.
Why is liquid not added first when charging a low-pressure chiller from a deep vacuum?
Answer: The liquid would boil rapidly, chill the tubes and could freeze the water inside. At very low pressure, liquid refrigerant flashes to vapor and pulls the temperature down. Vapor first raises the pressure above the point where water in the tubes could freeze.
What is the leak rate threshold for comfort cooling chillers covered by the leak repair rule?
Answer: 10%. Comfort cooling appliances, including most building chillers, must be repaired when the leak rate exceeds 10%.
What does ASHRAE Standard 15 require in mechanical equipment rooms?
Answer: A refrigerant detector that triggers an alarm and ventilation. ASHRAE 15 requires refrigerant detectors in machinery rooms that sound an alarm and start mechanical ventilation when refrigerant builds up.
Which refrigerant is commonly used in new low-pressure centrifugal chillers as a low-GWP replacement for R-123?
Answer: R-1233zd(E). R-1233zd(E) is a low-pressure refrigerant with very low GWP and an A1 safety classification. It is widely used in new centrifugal chillers.