R-454B vs R-410A vs R-32: What Technicians Need to Know
Short version: R-410A is being replaced in newly manufactured residential and light commercial air conditioners because its GWP is far above the AIM Act limit of 700 (equipment made before 2025 may still be installed). R-454B and R-32 are the main replacements. Both are A2L (mildly flammable) refrigerants.
| R-410A | R-454B | R-32 | |
|---|---|---|---|
| Type | HFC blend (R-32 + R-125) | HFC/HFO blend (R-32 + R-1234yf) | Single-component HFC |
| GWP (AR4) | 2,088 | 466 | 675 |
| ASHRAE safety class | A1 | A2L | A2L |
| Charging | As liquid | As liquid | Liquid or vapor (single component) |
Can you put R-454B in an R-410A system?
No. A2L refrigerants may only be used in equipment designed and listed for them. Never mix refrigerants or convert a system unless the manufacturer approves it.
Servicing A2L systems safely
- Use spark-free recovery machines, vacuum pumps and leak detectors rated for A2L refrigerants. Never use a halide torch.
- Recover the refrigerant and purge with nitrogen before brazing.
- Many indoor units include refrigerant leak sensors that start the blower and stop the compressor when a leak is detected.
- Keep ignition sources away and ventilate the work area.
On the EPA 608 exam
Expect questions on safety classes, which refrigerants are A2L and how to handle them. Read our A2L guide for the basics.
Source: EPA: Technology transitions
R-454B and R-410A practice questions
From our free question bank. Try each one before you open the answer.
1. How do HFC refrigerants such as R-134a and R-410A affect the environment?
- They deplete ozone faster than CFCs
- They have zero ozone depletion potential but can have a high global warming potential
- They have zero global warming potential
- They have the same impact as HCFCs
Show answer
B. They have zero ozone depletion potential but can have a high global warming potential. HFCs contain no chlorine, so they do not deplete ozone. Many of them are strong greenhouse gases, which is why the AIM Act phases down HFC production and limits their use in new equipment. Memory trick: O is for Ozone (the hole above us), G is for Greenhouse (the heat around us). HFCs score 0 on O but can score high on G.
2. Which of these refrigerants is an HFC?
- R-11
- R-123
- R-410A
- R-502
Show answer
C. R-410A. R-410A is a blend of two HFCs (R-32 and R-125). R-11 is a CFC, R-123 is an HCFC, and R-502 is a CFC-containing blend.
3. What safety marking is used on many cylinders of A2L (mildly flammable) refrigerants such as R-32 and R-454B?
- A red band or red marking on the cylinder
- An all-black cylinder
- A blue top
- No marking at all
Show answer
A. A red band or red marking on the cylinder. Cylinders of A2L refrigerants carry a red marking (often a red band on the shoulder) to warn that the contents are mildly flammable. Always use tools and recovery equipment rated for A2L refrigerants.
4. Which of these is a high-pressure refrigerant?
- R-11
- R-123
- R-410A
- R-1233zd(E)
Show answer
C. R-410A. R-410A and R-22 are high-pressure refrigerants used in comfort cooling and refrigeration. R-11, R-123 and R-1233zd(E) are low-pressure refrigerants used in centrifugal chillers.
5. Using recovery equipment made after November 15, 1993, what evacuation level is required for a high-pressure appliance (such as an R-22 or R-410A system) with less than 200 pounds of refrigerant?
- 0 inches of mercury (0 psig)
- 4 inches of mercury
- 10 inches of mercury
- 15 inches of mercury
Show answer
A. 0 inches of mercury (0 psig). High-pressure appliances with less than 200 pounds must be evacuated to 0 inches Hg, whatever the age of the recovery equipment. Older study guides listed separate rows for R-22; the current table in 40 CFR 82.156 does not. Memory trick: High pressure under 200 lb = zero: 0 inches, old or new equipment.
Learn it step by step: High-pressure refrigerants and pressure classes (Type II lesson, 8 min, with a short check at the end).