EPA 608 Memory Tricks: Easy Ways to Remember the Numbers

The EPA 608 exam is full of numbers that look alike. These short memory tricks help them stick. Each one is checked against the current rules, and every practice question with a trick shows it after you answer.

How to study smarter

  1. Start with Core. It is part of every certification, and many Type I, II and III questions build on it.
  2. Learn the why, not the answer letter. The test comes in several versions, and the 2026 question bank rewords many questions, so a question about R-22 may now mention R-32 or R-454B. Memorized answer patterns break; understanding does not.
  3. Learn numbers in families. 10-20-30, 80-90-4, 10-15-25: groups are easier to remember than single facts.
  4. Read every word. Watch for NOT, EXCEPT and "always". Eliminate the clearly wrong answers first.
  5. Use material that matches your exam. Old and new versions overlap until January 1, 2027. Ask your testing organization which one you will take.
  6. Aim for 80%. You need 70% (18 of 25) in each section. Practicing to 80% gives you a safety margin.

Core tricks

"Chlorine is the Culprit"Chlorine destroys ozone. CFCs (no hydrogen) are worst, HCFCs (with a "Helper" hydrogen) are less harmful, HFCs (no chlorine) do zero ozone damage.
O is for Ozone, G is for GreenhouseODP = damage to the ozone layer above us, measured against R-11. GWP = heat trapped around us, measured against CO2. An HFC can be 0 on ODP and high on GWP.
The three Rs: Remove, Rinse, Re-certifyRecover = remove it into a cylinder. Recycle = rinse it through filters on site; it stays with the same owner. Reclaim = re-certify it to AHRI 700 in a lab; then anyone can use it.
"'92 for the old gases, '95 for the new"Venting CFCs and HCFCs has been illegal since July 1, 1992; substitutes such as HFCs since November 15, 1995.
De minimis = tiny and accidentalA tiny, accidental release while correctly recovering (like connecting hoses) is allowed. Releasing any amount on purpose is not.
"80 and 125"Fill a cylinder to 80% at most, and never let it get hotter than 125°F.
Yellow top = caution, used refrigerantRecovery cylinders are gray with a yellow top. New refrigerant cylinders all share one light gray color, so read the label.
"Nitrogen for testing, never oxygen"Oxygen plus oil under pressure can explode. Use dry nitrogen with a regulator and relief valve.
Letter = toxic, number = flameA is lower toxicity, B is higher. 1 = no flame, 2L = "Little" (low burning velocity), 2 = flammable, 3 = very flammable. R-454B and R-32 are A2L; propane (R-290) is A3; R-123 is B1.
Azeotropes Act Alone, Zeotropes Zig-zagAzeotropes behave like one refrigerant. Zeotropes glide across a temperature range and can fractionate, so blends go in as liquid.
SuperHEAT = Hot vapor, SubCOOL = Cool liquidSuperheat is measured on the vapor leaving the evaporator; subcooling on the liquid leaving the condenser.
The Big ThreeA major repair removes the Compressor, Condenser or Evaporator.
608 stays put, 609 has wheelsSection 608 covers stationary equipment; Section 609 covers motor vehicle air conditioning.

Type I tricks

Type I is tinySmall appliances are factory-sealed with 5 pounds of refrigerant or less, about a bag of sugar.
"90 if it runs, 80 if it's dead, 4 inches either way"With recovery equipment made after November 15, 1993: recover 90% if the compressor works, 80% if it doesn't, or pull a 4-inch vacuum. Older equipment: 80% or 4 inches.
Dead compressor? Tap both sidesAccess both the high and low side, and heat and tap the compressor to free refrigerant from the oil.
Pierce and leavePiercing valves are temporary. Remove them after service, because they tend to leak.
84 open, 70 closedOpen-book Type I needs 84% (21 of 25) and never counts toward Universal. Proctored tests need 70% (18 of 25).

Type II tricks

10-20-30: Comfort, Commerce, IndustryLeak repair triggers for appliances with 50 lb or more of CFC or HCFC refrigerant: comfort cooling 10%, commercial refrigeration 20%, industrial process 30%. The trap on the test swaps 20 and 30.
30 to fix, 120 to shut downRepairs are due in 30 days, or 120 days if an industrial process must shut down.
Leaked more than it holds? Report by MarchAn appliance that leaks 125% or more of its charge in a year must be reported to EPA by March 1.
"Old machines say 4"With recovery equipment made before November 15, 1993, most rows are 4 inches Hg (zero for very high pressure and high pressure under 200 lb).
"Zero, Ten-Ten-Fifteen"With newer equipment: very high and small high-pressure (under 200 lb) = 0 inches. High 200 lb+ = 10, medium under 200 lb = 10, medium 200 lb+ = 15.
"Zero to open, five for oil"Bring the system to 0 psig or lower before a non-major repair, and 5 psig or lower for an oil change.
Passive is for 15 and underSystem-dependent recovery only on appliances with 15 pounds or less.
Fixed feels the suction, valve looks at the liquidFixed metering device: check charge by superheat. TXV: check by subcooling.
Air = upNon-condensables in the system push head pressure up.

Type III tricks

"High pushes out, low pulls in"Leaks on high-pressure systems blow refrigerant out. Low-pressure chillers run in a vacuum, so leaks suck air and moisture in.
"Ten to Test, Fifteen to Flip"Leak test a low-pressure chiller at no more than 10 psig, because the rupture disc bursts at 15 psig.
25 mm, any ageLow-pressure appliances must reach 25 mm Hg absolute, no matter when the recovery machine was made.
Cook the oil at 130Heat the oil to 130°F before draining to drive the refrigerant out of it.
Vapor first, no frozen tubesCharge vapor until the saturation temperature is above 32°F, then switch to liquid.
Moving water doesn't freezeKeep the water circulating (or drained) while recovering or evacuating.
Purge running a lot = leakThe purge unit removes air from the top of the condenser. If it runs more and more, air is getting in.

All the numbers in one place

NumberWhat it means
5 lbSmall appliance limit (Type I)
80% / 90% / 4 in HgSmall appliance recovery
80% · 125°FMax cylinder fill · max cylinder temperature
10 / 20 / 30%Leak triggers: comfort / commercial / industrial (50 lb+ CFC or HCFC)
30 / 120 daysRepair deadline / with industrial shutdown
125%Chronic leaker, report by March 1
0 · 10 · 10 · 15 in HgNew equipment: high <200 lb · high 200+ · medium <200 · medium 200+
25 mm Hg absoluteLow-pressure evacuation
0 psig · 5 psigBefore a non-major repair · oil change
15 lbMax charge for system-dependent recovery
10 · 15 psigLow-pressure leak test max · rupture disc
130°FHeat chiller oil before draining
70% (18/25) · 84% (21/25)Proctored pass · open-book Type I pass

Tricks written by the EPA 608 Practice Exam team and checked against 40 CFR Part 82, Subpart F. Exam changes: ACHR News.