EPA 608 Glossary: Key Terms in Plain English
The terms below come up again and again on the EPA 608 exam. Each definition is one or two sentences, in plain English.
- A2L
- ASHRAE safety class for refrigerants with lower toxicity and lower flammability (low burning velocity), such as R-32 and R-454B.
- A3
- Lower toxicity, higher flammability. Hydrocarbons such as R-290 (propane) and R-600a (isobutane).
- AHRI 700
- The purity standard reclaimed refrigerant must meet, verified by chemical analysis.
- AIM Act
- The 2020 law that phases down HFCs. Its rules apply on the job but are not tested on the Section 608 exam.
- Azeotrope
- A blend that behaves like a single refrigerant, with no temperature glide (for example R-502).
- CFC
- Chlorofluorocarbon. Contains chlorine and no hydrogen; highest ozone depletion potential (R-11, R-12).
- Chronically leaking appliance
- A covered appliance that leaks 125% or more of its full charge in a calendar year; must be reported to EPA.
- Comfort cooling
- Air conditioning that cools occupied spaces for people. Leak repair trigger: 10%.
- Commercial refrigeration
- Refrigeration in retail food and cold storage. Leak repair trigger: 20%.
- De minimis release
- A tiny, accidental release during a good-faith attempt to recover refrigerant, such as when connecting hoses. Not a violation.
- Evacuation
- Pulling a system into a vacuum to recover refrigerant or remove air and moisture.
- Fractionation
- When the parts of a zeotropic blend leak or boil off at different rates, changing the blend.
- Full charge
- The amount of refrigerant an appliance needs for normal operation.
- GWP
- Global warming potential: how much heat a gas traps compared with carbon dioxide.
- HCFC
- Hydrochlorofluorocarbon. Contains chlorine and hydrogen; lower ozone depletion than CFCs (R-22, R-123).
- HFC
- Hydrofluorocarbon. No chlorine, so zero ozone depletion, but often a high GWP (R-134a, R-410A).
- HFO
- Hydrofluoroolefin. Very low GWP; some are A2L (R-1234yf).
- High-pressure appliance
- Uses a refrigerant with a saturation pressure of 170–355 psia at 104°F, such as R-22 or R-410A.
- Industrial process refrigeration
- Refrigeration directly linked to industrial processes. Leak repair trigger: 30%.
- Low-pressure appliance
- Uses a refrigerant with a saturation pressure below 45 psia at 104°F, such as R-123. Usually centrifugal chillers.
- Major repair
- Work that removes the compressor, condenser or evaporator.
- Medium-pressure appliance
- Uses a refrigerant with a saturation pressure of 45–170 psia at 104°F, such as R-134a or R-124.
- Non-condensables
- Gases such as air that will not condense in the system; they raise head pressure.
- ODP
- Ozone depletion potential, measured against R-11.
- Piercing access valve
- A clamp-on valve used for temporary access to small appliances; remove it after service.
- Purge unit
- Removes air and other non-condensables from a low-pressure chiller's condenser.
- Reclaim
- Reprocess refrigerant to AHRI 700 purity, verified by lab analysis, so anyone can use it.
- Recover
- Remove refrigerant from a system and store it in an external container.
- Recycle
- Clean refrigerant for reuse with oil separation and filter-driers, usually on site.
- Rupture disc
- Safety device on a low-pressure chiller evaporator that bursts at about 15 psig.
- Self-contained recovery
- Recovery equipment with its own compressor that stores refrigerant in a pressurized cylinder.
- Small appliance
- Factory-sealed appliance with 5 pounds of refrigerant or less (Type I).
- Subcooling
- How far liquid refrigerant is below its condensing temperature.
- Superheat
- How far refrigerant vapor is above its boiling temperature.
- System-dependent recovery
- Recovery that relies on the appliance's own compressor or pressure. Allowed only on appliances with 15 pounds or less.
- Temperature glide
- The temperature range over which a zeotropic blend boils or condenses at one pressure.
- Venting prohibition
- The ban on knowingly releasing refrigerant: since 1992 for CFCs and HCFCs, since 1995 for substitutes.
- Very high-pressure appliance
- Uses a refrigerant with a saturation pressure above 355 psia at 104°F, such as R-23.
- Zeotrope
- A blend whose parts boil at different temperatures, so it has a temperature glide; charge it as liquid.